We are offering Electrical Control Panel Board. LOW VOLTAGE DISTRIBUTION BOARD (MCC-1 )
|
Function
|
Switching, protection and distribution of incoming power
|
|
Construction
|
The cabinets are made of steel sheet with front doors, painted, cabinet is designed in a modular manner consisting of arrays of switch gear units (cells) arranged vertically and separated by a cable way.
|
|
Enclosure
|
IP 50
|
Overall design and details
IDB Components
The IDB switchgear consists of the following basic units:
- Main power incoming compartment
- Bus Coupler compartment
- Full-Voltage Non-Reversing Starters (Circuit Breaker protected)
- Full-Voltage Reversing Starters (Circuit Breaker protected)
- Feeders
- Metering components and indications, local push buttons, switches.
MOTOR CONTROL BOARD (MCBS)
|
Function
|
Switching, protection, control and distribution of power to the frequency controlled motors.
|
|
Construction
|
Switch gear boards enclosed in steel sheet cabinets, suitable for inside installation in enclosed and ventilated electric room. Boards are systematically divided into a common section and strand sections. The cabinets are made of steel sheet with front doors, internally illuminated and with interlocking of doors. IP 31 panels. |
|
PLC Interface
|
Each drive will be connected to PLC controls by following signals. Ready and run feed back ( DI ) Analog speed reference ( AO) Forward and rev command ( DO ) |
|
Components
|
SFU Fuses Variable speed-controlled drives Line Choke at O/P Dynamic Brake Resistor when applicable Various control and power terminations |
PROGRAMMABLE LOGIC CONTROL EQUIPMENT ÃÆÃâÃâ ââ¬â¢ÃÆÃ¢â¬Å¡ÃâÃÂ¢ÃÆÃâÃâÃÂ¢ÃÆÃ¢Ã¢ââ¬Å¡Ã¬Ãâ¦ÃÂ¡ÃÆÃ¢â¬Å¡ÃâÃÂ¬ÃÆÃâÃâÃÂ¢ÃÆÃ¢Ã¢ââ¬Ã
¡ÃâÃÂ¬ÃÆÃ¢â¬Â¦Ã¢ââ¬Ã
â PLC
|
Function
|
The sequential control for the various functions of each casting floor drive, strand drive and the discharge drives shall be provided by Programmable Logic Controllers (PLC's). The various functions to be performed by this PLC system include, in general: Digital input treatment (pushbuttons, selector switches, limit and proximity switches, level switches, temperature switches, pressure switches, flow switches, AC drive signals, alarm signals) Digital output treatment (indication lamps, indicators, AC drive commands, solenoid valve commands) Analog to digital conversion and treatment (level signals, temperature transmitters, flow transmitters, motorized valve positions, variable drive speeds) Motor and drives start/stop logic Manual mode movements of casting, strand and discharge equipment Automatic mode movements of casting, strand and discharge equipment Automatic sequence logic Interlocking of individual items and interrelated equipment for safe and reliable operation Control and regulation of variable drive speeds, water flows depending on casting conditions Monitoring of "Ready to Cast" Conditions Alarm signalization |
|
Construction
|
The PLC systems will be located in air conditioned electrical rooms, mounted in steel sheet cabinets, suitable for inside installation
|
|
Main voltage
|
220 V AC from UPS
|
Overall design and details
|
PLC components
|
Mounting frame (chassis) Power supply CPU i.e. Central processing unit Memory module Communication modules Digital input modules Digital output module Analogue input module Analogue output module Counter modules |
The CCM parts controlled and/or interlocked by the PLCs' are:
- Tundish car travel
- Rigid Dummy Bar storage
- Mould oscillation
- Withdrawal and straightening unit
- Mould lubrication
- Hydraulic system (W/S unit)
- Spray cooling system
- Discharge and Pusher
|